Technical Data: KCD2-RR-Ex1General specifications
Signal type Analog input
Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30 V DC
Ripple within the supply tolerance
Rated current < 20 mA
Power consumption 0.35 W (24 V and 1 mA sense current)
Input
Connection terminals 1, 2, 3, 4
Line fault detection yes , at Pt100
Lead resistance ≤ 10 % of resistance value
Transmission range 0 ... 10 mA
Available voltage 9 V
Line fault detection 50 nA
Output
Connection terminals 5-, 7-, 6+, 8+
Current 0 ... 10 mA
Available voltage 0 ... 7 V
Fault signal 400 Ω, depending on lead disconnected (measuring current ≤ 1mA)
Transfer characteristics
Deviation Im ≥ 1 mA: ± 0.1 % of Rm or ± 0.1 Ω (the larger value is applicable)
Im 50 Ω and Im < 5mA: 30 Ω and Im < 5mA: 18 Ω and Im < 5mA: < 20ms
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21
Protection degree IEC 60529
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Mass approx. 100 g
Dimensions 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 in) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001